- Scope
- Federal
Provide one Pad Mounted Transformer 750 kVA, 13.2 kV /208Y/120 V.
Salient Characteristics: Furnish one (1) pad mounted, dead front, radial transformer, rated: ?
Capacity: 750 kVA ?
Phases: 3 ?
Primary Voltage: 13,200 V (15 kV class) ?Secondary Voltage: 208Y/120 V ?
Frequency: 60 Hz ?
Phase: Three phase ?
Cooling :ONAN ?
Fluid: Mineral oil 2.
Mandatory Physical Dimensions: The following dimensions are non negotiable: ?
Height: 63?? inches (up to 64?? inches) ?
Width: 65 inches ?
Depth: May varies (existing is 41 inches) The Contractor shall confirm with proposal the manufacturing dimensions, either in writing or by a shop drawing, for government approval.
3.
Mechanical and Construction Requirements: The transformer shall include: ?Stainless steel tank, cabinet and hardware (304) ?
Dead front construction ?
Pentahead security hardware ?
ANSI 61 Grey color to match with existing enclosure ?
Welded tank construction, sealed and pressure tested ?
1-inch Oil drain valve located on the primary side with 3/8-inch water sampler (required due to secondary side cable congestion) ?
Arc-flash and safety labeling ?
Lifting lugs and jacking pads ?
Nameplate per ANSI C57.12.00 4.Electrical Requirements: ?
Primary bushings: (6) 200 A load break wells with inserts for (3)LV and (3) 10KV arresters ?
Secondary bushings: NEMA spade w/ supports terminals 10holes (3) LV and (1) neutral per ANSI ?
Configuration: Radial Feed ?
Impedance: Standard ANSI values for 750 kVA ?
Taps: ?2 x 2.5% (standard 5 position no load tap changer) 5.Protection and Monitoring: The transformer shall include: ?
Bayonet fuse with isolation link?
Current limiting fuses ?
Load break switch (2 position minimum) ?
Nitrogen pressure gauge, test port and blanket ?
Temperature gauge ?
Pressure vacuum gauge ?
Liquid level indicator ?
Schrader valve Note: All...
Official solicitation and documents
The full solicitation, any attachments, and the actual submission instructions live on the official listing, not on this page. Oppward summarizes public record data; it does not host or mirror the source documents.
Oppward is an independent service and is not affiliated with, endorsed by, or sponsored by SAM.gov or any government agency. This page is a plain-English summary of public record data; the linked source above is the authoritative listing.
How to bid on this
This is a contract solicitation, not a grant. To bid, you submit a proposal (usually a price and a description of how you would do the work) directly to the government, through the channel the official listing specifies, not through Oppward.
- Make sure your business has an active SAM.gov registration. You cannot be paid on a federal contract without one.
- Read the full solicitation on the official listing above, especially the scope of work, not just this summary. Our guide to reading a solicitation walks through what to look for.
- Check the set-aside listed above and confirm your business actually qualifies for it before you spend time on a proposal. See our guide to set-asides if the category is unfamiliar.
- Submit your proposal by the deadline, using the exact submission method the official listing states. A technically on-time bid sent the wrong way is often treated as late.
Get contracts like this one matched to your business, free.